EXPLOSION PROOF ELECTRO-MAGNETIC STARTER of EPES type
Specifications
№ | Parameter |
ПВЭМ 160 |
ПВЭМ 250 |
ПВЭМ 400 |
ПВЭМ 630 |
---|---|---|---|---|---|
1 | Number of supply mains phases | 3 | |||
2 | Started rated current, A | 160 | 250 | 400 | 630 |
3 | Rated voltage of supply system, V |
380 / 660 660 / 1140 |
380 / 660 660 / 1140 |
380 / 660 660 / 1140 |
660 /1140 |
4 | Supply frequency, Hz | 50 | |||
5 | Insulation resistance of supply circuits, MOhm | ≥10 | |||
6 | Transient resistance of ground terminals, Ohm | ≤1 | |||
7 | Voltage of control and alarm circuits, V | ~127 В | |||
8 | Power consumption, no more, kW |
60 |
|||
9 | Marking of explosion protection | РВ Exd[ia]ia l | |||
10 | Jacked protection level | IP54 | |||
11 | Full specified lifetime, years | 15 | |||
12 | Overall dimensions, not more than (WxHxD), mm | 390 х 757 х 672 | 650 х 930 х 695 | ||
13 | Weight, kg, no more than | 227 | 390 |
Complectation
Starter is intended for application in three-phase electrical mains of industrial AC networks with isolated neutral of transformer in the coal mines, gas (methane) and/or and pulverized coal hazardous, for remote and direct start and stop of three-phase asynchronous electric motors, and also for protection against their overload and short-circuit currents in outgoing power circuits.
The design and electrical circuit of the PVEM starter meets all modern requirements for starting equipment.
The basis of the EPES starter is a modern microcontroller-based terminal of protecting connections MTCP-1200 that allows making the starter an intelligent device with adjustable in wide range protection settings, keeping emergency logs and the ability to control and output information to the dispatcher's console.
PEVM provides:
- Manual emergency shutdown of power cable lines;
- automatic protecting cutout of power cable lines when protection is activated;
- communication via wire line carrier with automation devices of local system through Modbus RTU interface;
- protection against unauthorized access to change system settings;
- local and remote control mode;
- archiving data of switching on and off and emergency situations.
- Automatic protecting cutout;
- three-stage OP:
- electric motor protection against overload and motor shaft seizure and part-phase operating mode;
- motor overheating protection;
- ground conductor integrity control and conductor of remote control of the power supply cables;
- protection against loss of control in case of breakage or closure of control cable conductors;
- preliminary insulation testing (BRU) of the power cable lines with blocking the voltage supply to line with the reduced insulation resistance.