XX
/
Powerof frequency converter, kW
XXX
-
Supply voltage, V
UHL5
Climatic performance according to GOST 15150-69

Specifications

Основные технические параметры:

№, п/п Параметр Значение
1 Numberof phases of supply mains 3
2 Rated voltage of supply system, V 690
3 Supply frequency, Hz 50
4 Number of connected Bf, pcs 1 (2)
5 Total power of BF engines, KW 50 /75 / 90
6 Method of connecting power cables БРС
7 Port capacity RS-485 2
8 Communication protocol (field communication) ModBUS RTU
9 Cooling method air
10 Overall dimensions, mm, not more (length, width, depth) 1120 х 1385 х 1000
11 Weight in kg, no more than 850
12 Marking of explosion protection РВ Ех d [ia ор is] l
13 Protection level of jacket according to GOST 14254, not lower than IP 54
14 Operating ambient air temperature value, C -10 .. +45

Complectation

Frequency converter of ventilation fan of FCVF type is intended for automatic maintenance of specified booster fan (BF) capacity in networks of 690 V with frequency of 50 Hz at coal mining enterprises gas and/or dust hazardous.

The device is made with spark-safe remote control circuits, it has the explosion-proof design and protection marking PB Exd[ia]ia I. The shell structure provides ingress IP54 protection according to GOST 14254-96.

It provides:

  • Operational localand remote control;
  • possibility to connect two motors to one converter;
  • operating or standby mode of drive operation;
  • connection to main optical communication link;
  • electrical protections* (27,50, 59, 79, etc.);
  • preliminary insulation testing of outgoing lines (BRU mode);
  • protection against loss of control;
  • control of air leakage from the ventilation pipe;
  • control of vibration accelerations of BF motor;
  • protection against BF shaft seizure.

Operating conditions:

  • Ambient air temperature -10...+35°C;
  • relative air humidity up to 100% at temperature +35°C;
  • absence of sharp jerks and shocks;
  • dust content in ambient air is not more than 1000 mg/m3;
  • working position in space is horizontal, deviation from
  • the working position up to 15 degrees in any direction is allowed.

Reliability indicators:

  • Average time between failures - not less than 8000 h;
  • established resource beforefirst major overhaul - not less than 65000 h;
  • average total service life - not less than 15 years;