REMOTE CONTROL UNIT of RCU-02 type
Specifications
№ |
Parameter | Value |
---|---|---|
1 | Rated voltage, V | 110 /220 |
2 | Frequency of supply voltage, Hz | 50 |
3 | Maximum power consumption, W | 5 |
4 | Nominal consumption current, A | 0,035 |
5 | Operating voltage range of supply network from Unom % | 85..110 |
6 | Minimum seal-in voltage from Un, % | 65 |
7 | Mechanical wear resistance of block elements, on/off cycles | 20000 |
8 | Intrinsic safety parameters according to GOST 30852.10 |
Um ≤ 250В; U0 ≤ 17,5V; l0 ≤ 107mA; СО ≤ 1uf; L0 ≤ 1Оmh |
9 | Unit weight, no more than, kg | 0,45 |
10 | Overall dimensions, mm | 100 х 45 х 113 |
Complectation
Remote control unit of the RCU is an EX-component. The unit is designed for transmission of discrete signals from elements located in explosion hazard zone to devices located in the explosion-proof zone. Sources of input signals can be sensors, limit switches and remote control panels. RCU unit has explosion protection marking [Ex ia] IU and be installed inside the explosion-proof jackets with a degree of protection not lower than IP54, or on the surface of mines beyond the explosion hazard zone.
IMU provides the following protection types:
- protection against loss of control in case of the short-circuit or wires breakage of the remote control circuit;
- protection against self-switching in case of short-term increase of supply voltage <150% of the rated one;
- activation of the executive component at grounding resistance <20 Ohm; retention of executive component at grounding resistance <25 Ohm;
- deactivation of executive component at grounding resistance <26 Ohm;